Analysis of the Effect of Unbalanced Load on Neutral Current, Power Losses and Efficiency in Distribution Transformer

(1) * Hartono Hartono Mail (Politeknik Penerbangan Surabaya, Indonesia)
(2) Rifdian Indrianto Sudjoko Mail (Politeknik Penerbangan Surabaya, Indonesia)
(3) Slamet Hariyadi Mail (Politeknik Penerbangan Surabaya, Indonesia)
(4) Tekat Sukomardojo Mail (Politeknik Penerbangan Surabaya, Indonesia)
(5) Siti Julaihah Mail (Politeknik Penerbangan Surabaya, Indonesia)
*corresponding author

Abstract


630 kVA, 20 kV/400 Volt transformer is a distribution transformer that supplies electrical loads at the Aviation Polytechnic of Surabaya. In a distribution transformer if the inter phase load is unbalanced there will be a neutral current flowing in the neutral wire.  This load imbalance is caused by single-phase loads on a 220 Volt low voltage network. The current flowing in the neutral of this transformer causes losses, namely due to the presence of neutral current in the neutral conductor of the transformer and losses due to neutral current flowing to the ground. After analyzing the peak load during the day of 79.92% and load imbalance during the day of 12.23%, then there is a neutral current of 181 Amperes and losses due to neutral currents flowing to the ground of 7, 26%, and transformer efficiency  at the day of 88.5 %.


Keywords


Unbalanced Load, Neutral Current, Losses, Efficiency

   

DOI

https://doi.org/10.47679/jrssh.v5i1.370
      

Article metrics

10.47679/jrssh.v5i1.370 Abstract views : 201 | PDF views : 121

   

Cite

   

Full Text

Download

References


B.L. Theraja, A.K. Theraja. (1995). A Text Book of Electrical Technology, Vol II, AC & DC Machines. Nirja Construction & Development Co. (P) LTD Ram Nagar, New Delhi.

Edwell T. Mharakurwa, George N. Nyakoe, A.O. Akumu. (2018). Thermal Modeling of Power Transformer with Unbalanced Loading. Pan African University Institute for Basic Science and Technology (PAUSTI), IEEE Press. https://doi.org/10.1109/PowerAfrica.2018.8521168

Sardono Sarwito, Semin, Muhammad Hanif. (2017). Analysis of Unbalanced Load of Three Phase Transformer Feedback 61-103 Performance on The Various Connection Windings. Proceedings of the International Conference on Advanced Mechatronics, Intelligent, Manufacture, and Industrial Automation (ICAMIMIA), IEEE Press. https://doi.org/10.1109/ICAMIMIA.2017.838575

Stevenson Jr., William D., Kamal Idris. (1994). Electric Power System Analysis. Erlangga.

Sudaryanto Sudirham. (1991). Effect of Current Imbalance on Power Shrinkage on the Line. Bandung: ITB, Implementation Team of PLN - ITB Cooperation.

Sulasno. (2009). Electrical Energy Conversion Engineering and Regulatory Systems. Graha Ilmu, Semarang.

Wijaya, M. (2001). Fundamentals of Electrical Machines. Jakarta: Djambatan.

Zuhal. (1991). Basic Electric Power. Bandung: ITB.


Refbacks

  • There are currently no refbacks.


Copyright (c) 2025 Hartono Hartono, Rifdian Indrianto Sudjoko, Slamet Hariyadi, Tekat Sukomardojo, siti Julaihah

Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 International License.

______________________________________________________________________________________________

Journal of Research in Social Science And Humanities

Published by Utan Kayu Publishing

Lucky Arya Residence 2 No. 18
Jalan HOS. Cokroaminoto Kab. Pringsewu
Lampung - Indonesia, Postal code 35373

Email: jurnal.jrssh@gmail.com